Temperature Regulators For Heating & Cooling Applications
W91 • Non-Indicating
W94 • Indicating - With Dial Thermometer
Used For Heating with Steam or for Cooling with Water along with Mixing/Diverting options as well as Domestic Hot Water Valves upon request.
Normally Open Valves are used for HEATING, so the valve stem closes (in-to-close) Fail position is (Normally Open)
Single-Seated Balanced Valves are used for HEATING Applications (normally steam) where tighter shut-off is required. Leakage rate is approximately 0.01% of the maximum capacity (Class IV shut-off).
Normally Closed Valves are used for COOLING, so the valve stem opens (in-to-open) Fail position is (Normally Closed)
Double-Seated Balanced Valves are used for COOLING Applications where larger flow rates of water are required, and a small leakage rate through the valve is normally acceptable. Leakage rate can be up to 0.5% of the maximum valve capacity (Class II shut-off).
Model W91 Non-Indicating No Dial Direct Acting Heating Regulator is ideal for regulating the temperature of tanks, process steams and various types of industrial equipment.
Model W94 Indicating With Dial Direct Acting Heating Regulator is ideal for regulating the temperature of tanks, process steams and various types of industrial equipment.
Copper Material (standard) on all Sensing Bulbs
1" NPT Brass Union Hub
Stainless Steel Sensing Bulbs Available Upon Request
Watson McDaniel Valve Model |
Pipe Size Connection |
Select Temperature Range |
Select Capillary Length | |
---|---|---|---|---|
W91 Heating (Non Indicating No Temp Dial) | Add to RFQ |
Watson McDaniel Valve Model |
Pipe Size Connection |
Select Temperature Range |
Select Capillary Length | |
---|---|---|---|---|
W94 Heating (Indicating With Temp Dial) | Add to RFQ |
Model W91 Non-Indicating No Dial Direct Acting Cooling Regulator is ideal for regulating the temperature of tanks, process steams and various types of industrial equipment.
Model W94 Indicating With Dial Direct Acting Cooling Regulator is ideal for regulating the temperature of tanks, process steams and various types of industrial equipment.
Copper Material (standard) on all Sensing Bulbs
1" NPT Brass Union Hub
Stainless Steel Sensing Bulbs Available Upon Request
Watson McDaniel Valve Model |
Pipe Size Connection |
Select Temperature Range |
Select Capillary Length | |
---|---|---|---|---|
W91 Cooling (Non-Indicating No Temp Dial) | Add to RFQ |
Watson McDaniel Valve Model |
Pipe Size Connection |
Select Temperature Range |
Select Capillary Length | |
---|---|---|---|---|
W94 Cooling (With Indicating Temp Dial) | Add to RFQ |