Safgard 250 Series Low Water Cut-Off
Commercial and Industrial Applications
       
 
       
Safgard 250 Series
  • No Moving Parts in Boiler Water
  • Controls Boiler Feed Pump
  • Maintains Recommended Water Level
    in Boiler
  • Available with Water Column Body or
    for Boilers with Separate Water Columns
  • Accommodates Boilers to 250 PSI
Specifications Model 250
Primary Relay 10 FLA, 60 LRA
Pump Relay 20 FLA, 120 LRA
Switch Contacts DPST
Power Consumption 13 VA
Max. Steam Pressure 250 PSI
       
MODEL VOLTAGE MANIFOLD DESCRIPTION/OPERATION
250 120 VAC 250C Operates boiler feed pump to maintain water level between middle and upper probes. Burner circuit contacts open if water drops below bottom probe. Automatically restarts burner on return of normal water level. Control box and (3) EL 1214 probes included.
250WC 120 VAC 1214C-1

250M 120 VAC 250C Same as 250/250WC above with Manual Reset feature. Locks out burner circuit if water remains below bottom probe for 90 seconds. Manual reset will not trip due to power failure. Control box and (3) EL 1214 probes included.
250MWC 120 VAC 1214C-1
     

 
Click here for Safgard low water crossover chart
 
 
 