Applications
The WD900 Disc Trap is designed to
automatically remove
condensate at a temperature that is
very close to that of the steam.
Freeze-proof installations can
be easily achieved because of the self
draining feature that is accomplished
by installing the unit in a vertical
orientation. Services
Superheated steam systems
Industrial Processing Equipment
High Pressure Drips
WD900 Thermodynamic Trap
Maximum
Operating Conditions Maximum Operating Pressure (PMO)
- 900 PSI
Maximum Operating Temperature (TMO) -
842°F
Design Pressure/Temperature Rating Maximum Allowable Pressure - 900
PSI
Maximum Allowable Temperature - 842°F
Materials
1 - Body - Alloy Steel, GR WC9
Seat - 420 SS
2 - Cover - Alloy Steel, GR WC9
3 - Strainer Cap - Alloy Steel, GR WC9
4 - Strainer - 300 Series SS
5 - Disc - 420 SS
6 - Gasket - 304 SS
7 - Studs - SA-193, GR B7
8 - Nuts - SA-194, GR 2H
9 - Insulating Can - Alum.
Order
Online Maximum
operating pressure of 900 PSI,
Low carbon Chrome-Moly body